NEC 220.82 Residential Electrical Load Calculator

Optional Method (Single Dwelling Unit) • Instant 100A–400A Panel Verdict for EV Chargers & Heat Pumps

100% Client-Side

Inputs auto-save locally in your browser. Zero server tracking.

sq ft

General lighting & receptacles @ 3 VA/sq ft = 6,000 VA

1,500 VA each = 3,000 VA

Fixed / Fastened-in-Place Appliances

Nameplate VA (edit as needed)
VA
VA
VA
VA
VA
VA
VA
VA
Add Custom Fixed Appliance
VA

Largest of 6 Rule: NEC 220.82(C) takes the larger of your Air Conditioning (100%) or your Electric Heating demand—never both.

VA

Include outdoor condenser/compressor + indoor air handler nameplate VA.

Amps
Required Dedicated Breaker (NEC 625.41)60A 2-Pole48A × 125% = 60.0A min
PASS
125.0A / 200A

Frequently Asked Questions — NEC 220.82 Load Calculations

Key code rules for residential service sizing, EVSE installations, and heat pump retrofits.

NEC Article 220.82 (Optional Method) is designed for single-family dwellings served by a 100A or larger service. Instead of applying separate demand tables for ranges, dryers, and fixed appliances like the Standard Method (NEC 220 Part III), 220.82 sums all general lighting, small appliance, laundry, and fixed appliance loads together, takes the first 10,000 VA at 100%, and applies a 40% demand factor to the remainder—then adds the largest single heating or cooling load plus EVSE. Because it better reflects residential diversity, the Optional Method typically yields a lower, more realistic service amperage.